Abstract:
This recommended practice provides calculation methods to conservatively evaluate the feasibility for an existing installed dry-type or liquid-filled transformer, to supp...Show MoreScope:This recommended practice applies only to two winding transformers covered by IEEE Std C57.12.00, IEEE Std C57.12.01, and NEMA ST20. It does not apply to rectifier transf...Show More
Purpose:The purpose of this document is to establish uniform methods for determining the capability of transformers to supply nonsinusoidal load currents of known characteristics...Show More
Metadata
Abstract:
This recommended practice provides calculation methods to conservatively evaluate the feasibility for an existing installed dry-type or liquid-filled transformer, to supply nonsinusoidal load currents as a portion of the total load. This recommended practice also provides necessary application information to assist in properly specifying a new transformer expected to carry a load, a portion of which is composed of nonsinusoidal load currents. A number of examples illustrating these methods and calculations are presented. Reference annexes provide a comparison of the document calculations to calculations found in other industry standards. Suggested temperature rise calculation methods are detailed for reference purposes.
Scope:
This recommended practice applies only to two winding transformers covered by IEEE Std C57.12.00, IEEE Std C57.12.01, and NEMA ST20. It does not apply to rectifier transformers
Purpose:
The purpose of this document is to establish uniform methods for determining the capability of transformers to supply nonsinusoidal load currents of known characteristics.
Date of Publication: 15 August 2008
Electronic ISBN:978-0-7381-5414-5
ICS Code: 29.180 - Transformers. Reactors