Abstract:
This standard covers enclosed low-voltage AC power circuit breakers of the stationary or draw-out type of two- or three-pole construction, with one or more rated maximum ...Show MoreScope:The scope of this standard includes enclosed low-voltage ac power circuit breakers, as follows: 1) Stationary or draw-out type of two- or three-pole construction, with on...Show More
Metadata
Abstract:
This standard covers enclosed low-voltage AC power circuit breakers of the stationary or draw-out type of two- or three-pole construction, with one or more rated maximum voltages of 635 V (600 V for units incorporating fuses), 508 V, and 254 V for application on systems having nominal voltages of 600 V, 480 V, and 240 V; with unfused or fused circuit breakers; manually or power operated; and with or without electromechanical or solid-state trip devices. It deals with service conditions, ratings, functional components, temperature limitations and classifications of insulating materials, insulation (dielectric) withstand voltage requirements, test procedures, and application.
Scope:
The scope of this standard includes enclosed low-voltage ac power circuit breakers, as follows: 1) Stationary or draw-out type of two- or three-pole construction, with one or more rated maximum voltages of 635 V (600 V for units incorporating fuses), 508 V, and 254 V for application on systems having nominal voltages of 600 V, 480 V, and 240 V. 2) Unfused or fused type; 3) Manually operated or power operated, with or without electromechanical or solid-state trip devices.
Date of Publication: 21 May 1991
Electronic ISBN:978-0-7381-1050-9
Persistent Link: https://ieeexplore.ieee.org/servlet/opac?punumber=2263